BCAB #1703 - Application of Part 7 to Townhomes

Last updated on March 24, 2016

November 24, 2011

BCAB #1703

Re: Application of Part 7 to Townhomes

Project Description

The project consists of 4 strata titled dwelling units in a single building, each suite separated by a fire separation with a 1 hour fire resistance rating. Each suite has a separate building drain.

Reason for Appeal

A plumbing drain and vent are shared between 2 units.

Appellant's Position

The appellant contends that the plumbing and building codes do not have any requirement that a plumbing system be designed for a single suite and that interconnection of drainage and venting systems between suites is permitted.

Building Official's Position

The building official maintains that since each suite has been provided with a separate building drain, the plumbing code requires drainage and vent pipe sizing, including hydraulic loads to be designed on a per suite basis. The plumbing system should be designed as though each suite is a separate building, and each suite should have its own drainage system, without interconnection between suites. 

Appeal Board Decision #1703

It is the determination of the Board that although each suite has been provided with a separate building drain, there is no requirement for separation of drainage and venting systems where a building contains more than one dwelling unit therefore, interconnection of drainage and venting systems between suites is permitted.

George Humphrey, Chair